Crestron GL-EXP-DIMU-CN Green Light Universal Dimmer Expansion Module for Cresnet Communications
Crestron GL-EXP-DIMU-CN Green Light Universal Dimmer Expansion Module for Cresnet Communications
The GL-EXP-DIMU-CN is a single-channel universal dimmer expansion module that allows for added lighting zones without an additional cabinet install. The expansion module controls electronic and magnetic low-voltage, LED, incandescent, and 2- wire fluorescent loads. Utilizing proprietary zero-cross filter technology, the GL-EXP-DIMU-CN compensates for line voltage and frequency fluctuations to provide immunity to power line noise and a dramatic reduction in lamp flicker.
Auto-Detecting Universal Dimming: Under normal operation, the GL-EXP-DIMU-CN detects the connected load type and selects the appropriate operating mode automatically. Reverse phase (trailing edge) mode supports incandescent and electronic low-voltage load types, while forward phase (leading edge) mode handles magnetic low-voltage and other inductive load types. Center phase mode is also available, combining reverse and forward phase load control to address special cases. The operative mode is indicated by two LEDs located on the front panel.
Cresnet® Communications: The GL-EXP-DIMU-CN interfaces with a Crestron control system via Cresnet. Cresnet is a simple 4-wire network bus that provides the communications backbone for a system of Crestron lighting dimmers, switches, keypads, shades, thermostats, and other devices.
Emergency Lighting Control: The GL-EXP-DIMU-CN is UL® 924 listed for use in controlling an emergency lighting load. In the event of a power failure, a contact closure from a power loss sensor (GLS-PLS-120/277, sold separately) activates the override mode in the GL-EXPDIMU-CN to turn on the lighting load if it is off (assuming line power is supplied by a backup power source). The override dimming level can be preset to any value when commissioning the lighting system, so even if the load is already on prior to a power failure, it will change to the preset level when override mode is activated.
Plenum Rated NEMA Enclosure: The GL-EXP-DIMU-CN is designed to be mounted to a vertical surface and is UL 2043 compliant to allow for installation in an environmental air-handling space above a suspended ceiling. Conduit knockouts are provided on the bottom and lower sides of the unit. All connections are made via screw terminals behind the front cover.
- Single-channel universal lighting dimmer
- Crestron® system integration via Cresnet® communications
- Supports dimmable LED, incandescent, electronic low-voltage, magnetic low-voltage, and 2-wire fluorescent lighting loads
- Rated 16 A at 100-277 VAC
- Auto load type detection
- Forward and reverse phase modes
- Zero-cross filter technology for reduced lamp flicker
- Extreme stability under noisy power line conditions
- Built-in air gap relay
- Closure-activated override mode
- UL® 924 listed for emergency lighting control
- Surface mountable NEMA Type 1 enclosure
- Mounts on a wall panel or above a suspended ceiling
- UL 2043 listed for installation in an environmental air handling space
Specifications
- Load Control
- Dimmer Channels: 1
- Load Rating: 16 A
- Line Voltage: 100-277 VAC, 50/60 Hz
- Dimmable Load Types: Incandescent, LED, electronic low-voltage, magnetic low-voltage, 2-wire fluorescent
- Communications
- Cresnet : Cresnet slave mode
- Connections
- NEUT: (3) Captive screw terminals; Neutral connections for feed and load; 24 to 10 AWG (0.25 to 4.0 mm²) wire size
- LINE: (2) Captive screw terminals; Line power feed input and pass-through; 24 to 10 AWG (0.25 to 4.0 mm²) wire size
- DIM: (1) Captive screw terminal; Dimmed load output; 24 to 10 AWG (0.25 to 4.0 mm²) wire size
- OVERRIDE:
- (2) Captive screw terminals; Low-voltage contact closure sensing input; Activates override mode when a closure is sensed;
- 26 to 14 AWG (0.14 to 1.5 mm²) wire size; For use with Class 2 wiring only
- CRESNET:
- (4) Captive screw terminals; Cresnet slave port (communications only, does not use Cresnet power);
- 26 to 14 AWG (0.14 to 1.5 mm²) wire size; For use with Class 2 wiring only
- Ground: (1) 3-terminal grounding block
- Controls and Indicators
- PWR : (1) Green LED, indicates line power is applied to either LINE terminal
- NET: (1) Yellow LED, indicates Cresnet network communication
- ERR: (1) Red LED, indicates a variety of error conditions via blinking patterns (refer to the installation guide)
- ON/OFF: (1) Pushbutton and (1) red LED, pushbutton toggles the load output on and off (press and hold to cycle the dimming level up and down), LED indicates the load output is energized
- FWD: (1) Red LED, indicates forward phase mode (or center phase mode if REV indicator is also on)
- REV: (1) Red LED, indicates reverse phase mode (or center phase mode if FWD indicator is also on)
- RESET: (1) Pushbutton, initiates hardware reset
- SW1: (1) Two-position slide switch (behind front cover), enables/disables the zero-cross detection filter (disabled by default)
- SW2: (1) Two-position slide switch (behind front cover), not used
- SW3, SW4: (2) Two-position slide switches (behind front cover); selects auto detect (default), forward phase, reverse phase, or center phase dimming mode
- Environmental
- Temperature: 32° to 104° F (0° to 40° C)
- Humidity: 10% to 90% RH (noncondensing)
- Construction
- Enclosure: NEMA Type 1, galvanized steel with gray matte powder coated removable front cover panel, extruded aluminum heat sink on rear, (2) integral mounting flanges, (4) 0.5 in. (13Â mm) or 0.75 in. (19Â mm) conduit knockouts on bottom and lower left & right sides
- Mounting: Surface mount, must be oriented upright and mounted to a vertical surface with 6Â in. (153Â mm) minimum spacing above and below for proper ventilation and heat dissipation
- Dimensions
- Height: 8.78 in. (223 mm)
- Width: 6.39 in. (163 mm)
- Depth: 3.16 in. (81 mm)
- Weight
- 3.43 lb (1.56 kg)
- Compliance
- C(UL)US, UL 924, UL 2043, FCC Part 15 Class A commercial use